Comparison of Electrical Performance Parameters Between Rare Earth Aluminum Alloy Cables and Copper Cables

Comparison of DC Resistance at 20℃ between Rare Earth Aluminum Alloy Conductors and Copper Conductors

Copper Cross-section(mm2)

DC Resistance of CopperΩ

Cross-section of Rare Earth Aluminum Alloy(mm2)

DC Resistance of Rare Earth Aluminum AlloyΩ

10

1.83

16

1.91

16

1.15

25

1.20

25

0.727

35

0.868

35

0.524

50

0.641

50

0.387

70

0.443

70

0.268

120

0.253

95

0.193

150

0.206

120

0.153

185

0.164

150

0.124

240

0.125

185

0.0991

300

0.100

240

0.0754

400

0.0778

300

0.0601

500

0.0605

400

0.0470

630

0.0469

 

 

Current-carrying Capacity Comparison & Selection Table for Rare Earth Aluminum Alloy Cables and Copper Cables

Cable Type

Cable Current-Carrying Capacity(A)

Nominal Cross-section mm2

0.6/1kv

8.7/15kv

26/35kv

Copper

Rare Earth Aluminum Alloy

Copper Cable

Rare Earth Aluminum Alloy Cable

Copper Cable

Rare Earth Aluminum Alloy Cable

Copper Cable

Rare Earth Aluminum Alloy Cable

25

35

120

122

 

 

 

 

35

50

150

156

175

175

 

 

50

70

196

198

205

214

220

224

70

120

255

276

305

333

270

309

95

150

310

325

370

388

330

355

120

185

360

372

430

440

375

401

150

240

419

443

490

521

425

472

185

300

479

518

560

603

485

548

240

400

565

639

665

722

560

648

300

500

643

765

765

813

650

727

400

630

771

851

890

934

760

831

 